Introduction

The  4004-16OUT is a 16 channel analogue output solution which has been designed to operate with the NetPod 4000 series of data acquisition hardware. The systems will operate across any type of Ethernet LAN or directly to a PC using a suitable network cable.
The system is built up using independent 4 channel cards. The maximum update rate is only limited to the sampling rate of the analogue data acquisition systems. All of the output channels are synchronised to the operation of the analogue input channels.
NPAO16-1030 Card
+
-
Output
Card
Terminals
30 mA current loop
or +/- 10V output
signal
Load
Connecting an load circuit to the NPAO16-1030
0V
+/- Output
 Output Connection from the NPAO16-1030
The image below shows how to connect
to the NPAO16-1030 to obtain a voltage output
Pre-set Initialisation / Startup levels

Each output channel can be independently configured using the driver software to give a pre-set output level on initialisation. The card has an initial zero level initialisation value held for 2 seconds after which the preset level is output. Since the output signal can be predefined then

The initial output level is zero no matter which output signal type has been chosen.

Load Circuit

The maximum load resistance that can be directly connected to the the NPAO16-1030 is 350 Ohm.  
No Channels
4
Isolation
to 2 KV DC
Range
+/- 10V
+/- 30 mA
Protection
short circuit < 1 min
Resolution
0.3 mV
0.001 mA
Integral Non linearity
+/- 1 LSB
Power
< 1 W / Channel
Operation

The analogue output cards support both voltage and current output under control from the driver software. The update rate of the output signals is at the same rate as sampling rate of analogue input channels.

Installation Limitation

The 4004-16OUT supports 16 analogue output channels within a single instrument along with a single digital I/O card.

Output Signal Type Selection

The analogue output signal can be switched under software control between current and voltage without any user interaction on the card itself. The driver software must scan the network to obtain and store any new configuration details.

Test Results

The output errors shown below are worst case and are to be used as a guide only.
Setting
100 W
300 W
0 W
% Error
Full Scale
% Error
Full Scale
% Error
Full Scale
-30
-30.001
-29.989
-30.007
-0.05
0.05
-0.05
0
-0.001
-0.001
-0.001
-0.05
-0.05
-0.05
30
30.002
29.989
30.008
0.05
-0.05
0.04
Load Resistance
100 W
300 W
0 W
Fully Populated Instrument
1
2
3
4
5
6
7
Slot
NPAO16-1030
NPAO16-1030v101.ppp
Processor Card - NP-OT4000-100T
Specification
Output Signal Type Identification

The output signal type for each channel can be identified by the driver software. Signal operational details can be accessed and processed by third party applications.
NetPod 4000 Series - Analogue Output Solution

Analogue Output ± 10 V  Output ± 30 mA Software Selectable

Part Number    -  4004-16OUT
Data Acquisition Systems
Ethernet LAN / Fibre Optic
Data Recording
Computer
Analogue Output Module
Connection to a fibre optic LAN
Part No. 4004-16OUT
Media Converter
100BaseT - Fibre Network
Part Number    -  AMP-8-3U
Part No. 4004-16OUT
Part No. 4004-16OUT
High Voltage analogue output system
Output levels 0 - 600V

Remote control across the local area network.
Complete system control across the local area network.
Large channel count systems or widely distributed applications can be created and used across a LAN
Last updated:  Nov 2011
+
+
+
+
-
-
-
-
The image opposite shows the NetPod 4004-16OUT Analogue Output System





The image below shows the 4 Channel NPAO16-1030 Card